含双馈风电场的电力系统低频振荡模态与阻尼分析

王琪鑫,唐飞

分布式能源 ›› 2017, Vol. 2 ›› Issue (3) : 20-25.

PDF(818 KB)
PDF(818 KB)
分布式能源 ›› 2017, Vol. 2 ›› Issue (3) : 20-25. DOI: 10.16513/j.cnki.10-1427/tk.2017.03.004
学术研究

含双馈风电场的电力系统低频振荡模态与阻尼分析

作者信息 +

Low Frequency Oscillation Modes and Damping Analysis of Power System With Doubly Fed Wind Farm

Author information +
文章历史 +

摘要

In view of the uncertainty problem of the low frequency oscillation caused by the doubly fed wind farm's accesss to power grid under high permeability, this paper presents a method of eigenvalue analysis under two working modes. Firstly, we analyze the mechanism of the traditional low frequency oscillation, and then establish the double fed induction generator (DFIG) model in the DigSilent simulation platform. Finally, we analyze the simulation and the characteristic values of the doubly fed wind farm's access to power grid under different permeability. The results show that the damping ratio increases with the increase of wind power penetration under the operation mode of constant power at high wind speed, and under the operation mode of constant speed at low wind speed, the damping ratio increases with the increase of wind power penetration at first, but later it decreases with the increase of wind power penetration. The simulation of IEEE 9-Machine 3-bus system verifies the validity and correctness of this method.

关键词

电力系统 / 双馈风电机组(DFIG) / 低频振荡 / 小干扰稳定 / 特征值 / 阻尼特性 / electric power system / doubly fed induction generator(DFIG) / low frequency oscillation / small-signal stability / eigenvalue / damping characteristic

引用本文

导出引用
王琪鑫, 唐飞, WANG Qixin, . Low Frequency Oscillation Modes and Damping Analysis of Power System With Doubly Fed Wind Farm[J]. 分布式能源. 2017, 2(3): 20-25 https://doi.org/10.16513/j.cnki.10-1427/tk.2017.03.004
[J]. Distributed Energy Resources. 2017, 2(3): 20-25 https://doi.org/10.16513/j.cnki.10-1427/tk.2017.03.004

参考文献

[1]
HAGSTROM E, NORHEIM I, UHLEN K. Large-scale wind power integration in Norway and impact on damping in the Nordic grid[J]. Wind Energy, 2005, 8(3): 375-384.
[2]
ANAYA-LARA O, HUGHES F M, JENKINS N, et al. Influence of windfarms on power system dynamic and transient stability[J]. Wind Engineering, 2006, 30(2): 107-127.
[3]
TSOURAKIS G, NOMIKOS B M, VOURNAS C D. Effect of wind parks with doubly fed asynchronous generators on small-signal stability[J]. Electric Power Systems Research, 2009, 79(1): 190-200.
[4]
SLOOTWEG J G, KLING W L. The impact of large scale wind power generation on power system oscillations[J]. Electric Power Systems Research, 2003, 67(3): 9-20.
[5]
FAN L, MIAO Z, OSBORN D. Impact of doubly fed wind turbine generation on inter-area oscillation damping[C]//Power and Energy Society General Meeting—Conversion and Delivery of Electrical Energy in the 21st Century. Pittsburgh, USA: IEEE, 2008: 1-8.
[6]
AKHMATOV V. Analysis of dynamic behavior of electric power systems with large amount of wind power[D]. Copenhagen, Denmark: Electric Power Engineering Technical University of Denmark, 2003.
[7]
郭权利. 电力系统低频振荡[J]. 电力系统保护与控制2008, 36(22): 114-116.
GUO Quanli. Low frequency oscillation in power system[J]. Power System Protection and Control, 2008, 36(22): 114-116.
[8]
余一平闵勇陈磊. 多机电力系统强迫功率振荡稳态响应特性分析[J]. 电力系统自动化2009, 33(22): 5-9.
YU Yiping, MIN Yong, CHEN Lei. Analysis of forced power oscillation steady-state response properties in multi-machine power system[J]. Automation of Electric Power Systems, 2009, 33(22): 5-9.
[9]
陈磊闵勇胡伟. 基于振荡能量的低频振荡分析与振荡源定位: (一)理论基础与能量流计算[J]. 电力系统自动化2012, 36(3): 22-27.
CHEN Lei, MIN Yong, HU Wei. Low frequency oscillation source location based on oscillation energy: Part one,mathematical foundation and energy flow computation[J]. Automation of Electric Power Systems, 2012, 36(3): 22-27.
[10]
王锡凡方万良杜正春. 现代电力系统分析[M]. 北京:科学出版社,2003.
[11]
余耀南. 动态电力系统[M]. 北京:水利电力出版社,1985.
[12]
王梅义. 大电网系统技术[M]. 北京:水利电力出版社,1991.
[13]
袁季修. 电力系统安全稳定控制[M]. 北京:中国电力出版社,1996.
[14]
倪以信陈寿孙张宝霖. 动态电力系统的理论和分析[M]. 北京:清华大学出版社,2002.
[15]
刘豹. 现代控制理论[M]. 北京:机械工业出版社,2000.
[16]
SENJYU T, SAKAMOTO R, URASAKI N, et al. Output power control of wind turbine generator by pitch angel control using minimum variance control[J]. IEEE Transactions on Power and Energy, 2005, 154(2): 10-18.
[17]
MILLER N W, PRICE W W, SANCHEZ-GASCA J J. Dynamic modeling of GE 1.5 and 3.6 wind turbine-generators, GE—power system energy consulting[J]. General Electric Inter-national, Inc., Schenectady, 2003, 19(2): 11-18.

编辑: 谷子
PDF(818 KB)

Accesses

Citation

Detail

段落导航
相关文章

/