Influence of Distributed Generation on Voltage Quality of Distribution Network and Limit Access Capacity

ZHANG Xuhang,ZHANG Mengyao,HUANG Ruanming,ZHAO Lingguang,ZHAO Jingjing

Distributed Energy ›› 2017, Vol. 2 ›› Issue (5) : 19-23.

PDF(838 KB)
PDF(838 KB)
Distributed Energy ›› 2017, Vol. 2 ›› Issue (5) : 19-23. DOI: 10.16513/j.cnki.10-1427/tk.2017.05.003
Basic Research

Influence of Distributed Generation on Voltage Quality of Distribution Network and Limit Access Capacity

Author information +
History +

Abstract

The distributed generation (DG) access has changed the traditional power supply mode of the distribution network, and has a great impact on the voltage quality, relay protection, short-circuit capacity and power flow direction of the distribution network. In order to study the influence of DG access on distribution network and the maximum acceptable capacity of DG under the constraint of distribution network in various operating conditions, taking a typical 10 kV network as an example, this paper analyzes the effects of DG access on the voltage quality of distribution network;then, taking distributed limit access capacity as optimization objective, with considering the voltage deviation, voltage fluctuation, short-circuit current line, carrying capacity of line, power flow equations constraints and distributed output constraints, adopts particle swarm optimization algorithm to solve this optimization problem to obtain the maximum access capacity when the distribution network is connected to DG in multi node at the same time. The simulation and optimization results show that the proposed model and algorithm are effective.

Key words

distributed generation(DG) / limit access capacity / voltage quality / particle swarm optimization algorithm

Cite this article

Download Citations
Xuhang ZHANG , Mengyao ZHANG , Ruanming HUANG , et al . Influence of Distributed Generation on Voltage Quality of Distribution Network and Limit Access Capacity[J]. Distributed Energy Resources. 2017, 2(5): 19-23 https://doi.org/10.16513/j.cnki.10-1427/tk.2017.05.003

References

[1]
苏小玲韩民晓赵正奎,等. 配电网中分布式电源最大准入容量分析[J]. 电网技术201236(10):87-92.
SU Xiaoling, HAN Minxiao, ZHAO Zhengkui,et al. Research on maximum capacity of grid-connected distributed generation in distribution network[J]. Power System Technology201236(10):87-92.
[2]
国家能源局. 2015年光伏发电相关统计数据[EB/OL]. (2016-02-05)[2017-02-02].
[3]
国家能源局. 中国可再生能源领跑全球[EB/OL]. (2016-11-07)[2017-03-02].
[4]
中国能源网. 2015年中国能源年度记忆[EB/OL]. (2015-12-28)[2017-01-01].
[5]
上海市人民政府. 上海市能源发展“十三五”规划[EB/OL]. (2017-03-15)[2017-04-02].
[6]
王江海邰能灵宋凯,等. 考虑继电保护动作的分布式电源在配电网中的准入容量研究[J]. 中国电机工程学报201030(22):37-43.
WANG Jianghai, TAI Nengling, SONG Kai,et al. Penetration level permission of for DG in distributed network considering relay protection[J]. Proceedings of the CSEE201030(22):37-43.
[7]
王鲍雅琼陈皓. 含分布式电源的配电网保护改进方案综述[J]. 电力系统保护与控制201745(12):146-153.
WANG Baoyaqiong, CHEN Hao. Overview study on improving protection methods of distribution network with distributed generation[J]. Power System Protection and Control201745(12):146-153.
[8]
马晓博. 考虑配电网电流保护约束的分布式电源准入容量研究[J]. 中国电力201649(4):88-92.
MA Xiaobo. Study on maximum penetration level of distributed generation in distribution network by considering current protection[J]. Electric Power201649(4):88-92.
[9]
钟清高新华余南华,等. 考谐波约束下的主动配电网分布式电源准入容量与接入方式[J]. 电力系统自动化201438(24):108-113.
ZHONG Qing, GAO Xinhua, YU Nanhua,et al. Accommodating capacity and mode of distributed generation under harmonic constraint in active distribution networks[J]. Automation of Electric Power Systems201438(24):108-113.
[10]
于辉王心赵冬梅. 以改造配电网设备适应性为目的的分布式电源准入容量计算[J]. 电网技术201640(10):3013-3018.
YU Hui, WANG Xin, ZHAO Dongmei. Calculation of distributed generation permeability for the adaptability reform of distribution network equipment[J]. Power System Technology201640(10):3013-3018.
[11]
刘科研刘永梅盛万兴,等. 考虑电压约束的分布式电源接入配电网最大准入容量计算方法[J]. 电力自动化设备201636(6):81-87.
LIU Keyan, LIU Yongmei, SHENG Wanxing,et al. Maximal allowable DG penetration capacity calculation considering voltage constraints[J]. Electric Powcr Automation Equipment201636(6):81-87.
[12]
王威王晴虞殷树,等. 分布式电源接入配电网的极限容量计算研究[J]. 电力信息与通信技术201715(3):14-18.
WANG Wei, WANG Qing, YU Yinshu,et al. Research on the calculation of limit capacity of distributed generation in distribution network[J]. Electric Power ICT201715(3):14-18.
[13]
夏成军崔弘王强,等. 考虑静态安全约束的分布式电源准入容量计算[J]. 电网技术200933(16):96-100.
XIA Chengjun, CUI Hong, WANG Qiang,et al. Penetration capacity calculation for distributed generation considering static security constraints[J]. Power System Technology200933(16):96-100.
[14]
郑涛贾仕龙潘玉美,等. 基于配电网原故障定位方案的分布式电源准入容量研究[J]. 电网技术201438(8):2257-2262.
ZHENG Tao, JIA Shilong, PAN Yumei,et al. Research on allowed penetration level of DGs based on the traditional fault location methods[J]. Power System Technology201438(8):2257-2262.
[15]
邹宏亮韩翔宇廖清芬,等. 考虑电压质量与短路容量约束的分布式电源准入容量分析[J]. 电网技术201640(8):2273-2280.
ZOU Hongliang, HAN Xiangyu, LIAO Qingfen,et al. Penetration capacity calculation for distributed generation considering voltage quality and short circuit capacity constraints[J]. Power System Technology201640(8):2273-2280.
[16]
林海雪. 第4讲 电压波动和闪变标准[J]. 建筑电气201130(8):12-16.
LIN Haixue. Lecture four:Standards of voltage fluctuation and flicker[J]. Building Electricity201130(8):12-16.

Funding

Project supported by National Natural Science Foundation of China(51207087)